Maintenance¶
Maintenance mode temporarily removes selected devices from operation, for example before working on and disconnecting a battery pack. The marked device is no longer polled and raises no alarms. Other devices, inverter communication, MQTT and the display continue operating.
Settings¶
Each category has two settings:
- Maintenance active: Stops polling marked devices and excludes them from monitoring, alarms, charge control and inverter control.
- Send MQTT: For devices in maintenance, enables continued polling and MQTT publication.
Settings are separate for Data Devices and Group Devices.
-
Data devices: maintenance active
-
Data devices: publish MQTT data
-
Group devices: maintenance active
-
Group devices: publish MQTT data
-
Group Devices
Group-device selection is relevant only when group devices are enabled.
What Happens During Maintenance?¶
- No polling: No more read requests are sent. Last values stop updating and become invalid after a few seconds. Switching off or disconnecting the device will not produce communication or cell voltage alarms; this does not remove electrical hazards or replace safe isolation procedures.
- No alarms: Excluded from cell voltage, temperature, plausibility and cell voltage drop rules.
- No control: Excluded as a source for charging, discharging and inverter control.
- Other functions continue: Other devices, CAN communication, OneWire sensors, the display and MQTT for other devices work normally.
- Visibility: Maintenance status appears in the web app and as an MQTT
maintenanceflag.
Data-Device Maintenance with Groups Enabled
Groups using a maintained data device are also treated as in maintenance and excluded from control. The device is polled only if required by a non-maintained group or Send MQTT.
Send MQTT During Maintenance¶
Normally, no MQTT data is sent for maintained devices. Enabling Send MQTT keeps polling them and sends all normal values. The maintenance flag stays set so receivers such as Home Assistant recognise their status.
Only Relevant in Maintenance
Devices not marked for maintenance are already polled and published normally.