Operating Settings for the BSC

This chapter introduces the settings required to operate the BSC. Available settings may vary by firmware version.

Setup Assistant

The web app provides setup assistants for networking, MQTT, serial interfaces and the inverter. They guide you through the main steps and populate data-device mapping automatically.

1. Basic Settings

Basic settings are in the System menu, including Wi-Fi credentials and, if MQTT is used, MQTT broker details. Open Settings / System.

Further information: System Settings.

2. BMS Settings in the BSC

The following configuration is necessary for communication.

Read-Only Access

The BSC accesses BMS data only for reading. It never writes settings, configuration or other data to the BMS. The BMS therefore remains a functionally independent safety layer.

2.1 Configure the Serial Interface

Specify which BMS type is connected to which hardware interface. Example: a JK Inverter BMS connected to Serial 0:

  • Serial 0: JK Inverter BMS
  • Serial 1: unused
  • Serial 2: unused

Menu: Settings / Interfaces / Serial.

Multiple BMS Units

Several BMS units of the same type can share one interface. They are distinguished by addresses, configured in the next step (data-device mapping).

Further information: Serial Interfaces.

2.2 Set Up Data-Device Mapping

After assigning a BMS type to each serial interface, map each individual BMS and its specific address.

A data device is the BSC's internal representation of a physical device (BMS, Victron SmartShunt, etc.). Correct address mapping is necessary for communication. Each BMS needs a unique address, particularly when several units of the same type share an interface.

Menu: Settings / Interfaces / Data devices.

Configure the following for each data device:

  • Interface: Select the hardware interface (Serial 0, Serial 1, etc.).
  • Address: BMS-specific address (0–16).

    Check Address Configuration

    Addresses must be correct both on the BMS itself and in BSC data-device mapping. Read the BMS-specific address instructions carefully: requirements differ between BMS types.

  • Name (optional): A display name to identify the device throughout the BSC menus.

Example: two JK Inverter BMS units on Serial 0:

  • Data device 0: Serial 0, address 1, name "Lower battery"
  • Data device 1: Serial 0, address 2, name "Upper battery"

Further information:

3. Inverter Settings

These are the basic settings needed for communication between the BSC and inverter.

3.1 General Settings

Menu: Settings / Inverter & Charge Control / General.

  • BMS CAN-Bus Enable: Enables inverter communication.
  • CAN bus protocol: Select the protocol for your inverter, such as Victron or Pylontech. Most inverters require Pylontech.
  • Data source: Select the data devices whose data is processed and sent to the inverter. Processing can include aggregation of several sources or application of charge control rules.

    Value Sources

    Valuehandling settings specify the domain, source and aggregation for each measurement. If group devices are enabled, they can also be selected as sources.

  • Valuehandling category: Select which values come from which data devices and how they are aggregated. See Multi-BMS Valuehandling.

  • Basic data category: Set charging voltages and maximum currents for the entire system. Under Batterypack settings, capacity and maximum currents can also be set per data device.

Further information: Inverter Settings.

3.2 Charge Control Settings

See Charge Control.

4. Alarm Rules

Alarm rules monitor selected data-device values and activate triggers when limits are reached. They do not replace correct BMS settings, but allow an earlier response, for example:

  • Set inverter charging current to 0 A.
  • Switch a relay.
  • Send a notification: when MQTT is enabled, trigger states are published via MQTT and can be processed by automation software such as ioBroker or Home Assistant for notifications or control commands.

Further information: How Triggers Work.