Discharging
Configure discharge-current limits based on cell voltage, temperature, temperature profiles and per-pack current. Set pack currents under Inverter / Basic Data / Batterypack Settings. Temperature rules work like their charging equivalents.
Excessive Discharge Current per Pack¶
Automatically and dynamically adjusts discharge current to keep each battery pack within its configured per-pack discharge limit, protecting against overcurrent.
- Reduce discharging current if a pack exceeds its discharge-current limit
-
On/Off
-
Cell-Voltage-Dependent Discharge Reduction¶
Adjusts discharge current based on cell voltage to protect cells and their service life.
-
On/Off
-
Start below cell voltagemVReduction starts when the lowest cell voltage falls below this value.
-
End cell voltagemVWhen the lowest cell voltage falls below this value, discharging is limited to the minimum discharging current.
Note: this value must be below the start cell voltage. -
Minimum discharging currentA
-
- On/Off: Enables cell-voltage-dependent reduction.
- Start below cell voltage: Reduction starts when the lowest cell falls below this threshold.
- End cell voltage: At or below this voltage, current is reduced to the configured minimum.
- Minimum discharge current: Lower bound used below the end voltage.
Threshold Order
End cell voltage must always be lower than start cell voltage.
Temperature-Dependent Discharge Reduction¶
Up to 4 individually configurable temperature rules use active data or group sources. Cold-side reduction uses the minimum temperature; hot-side reduction uses the maximum.
- Uses the sources from the active data source (data devices or group devices).
Control uses the appropriate extreme for the direction: the minimum temperature when reducing from warm to cold, the maximum when reducing from cold to warm.- Temperature rules
- Rule 1
-
On/Off
-
Data-device sensors
-
Extended sensor sources
-
Extended sensors 0-31
-
Reduction start°C
-
Reduction end°C
- Data-device sensors: Sensors 0–5.
- Extended sources / sensors 0–31: Additional sensors, e.g. OneWire.
- Reduction start: Temperature where reduction starts, default 20.00 °C.
- Reduction end: Temperature where current reaches 0 A, default 0.00 °C.
Reduction is linear between thresholds and can work for rising or falling temperatures. See the charging examples, which apply analogously.
Temperature-Profile Discharge Reduction¶
A freely defined 10-point temperature profile assigns a maximum C-rate to each temperature. Interpolate linearly between points; below/above the profile, use its first/last point.
- Uses the sources from the active data source (data devices or group devices).
-
On/Off
-
Data-device sensors
-
Extended sensor sources
-
Extended sensors 0-31
-
Temperature profile
Show values
X (°C) Y (C) -30 0 -20 0.1 -10 0.2 -5 0.4 0 0.6 5 1 45 0.5 50 0.25 55 0.2 60 0
-
- Data-device sensors: Sensors 0–5 used in control.
- Extended sources / sensors 0–31: Additional sources such as OneWire.
- Temperature profile: 10 temperature/C-rate pairs. Temperature range −30 to 60 °C, step 0.1 °C; C-rate step 0.01 C.
Discharge current is C-rate × capacity (Ah) using capacities from Batterypack Settings, capped by the maximum discharge current. With no configured capacity, discharge current is limited to 0 A.