BSC Interfaces¶
Interface settings specify what is connected where. They do not decide how BMS/balancer data is used or when relays switch; configure those actions in alarm rules or inverter settings.
Relay Outputs¶
- Relay outputs
- Relay output 1
-
Activation behavior
-
Pulse durationms
-
Delays
-
Invert
-
Select triggers
- Relay output 2
-
Activation behavior
-
Pulse durationms
-
Delays
-
Invert
-
Select triggers
- Trigger on: Select the trigger (1–27) that switches the relay.
- Trigger behaviour: Permanent stays energised while the trigger is active; Pulse switches for the configured pulse duration.
- Pulse duration: 100–10000 ms, default 500 ms, used in Pulse mode.
- Delay: 0–254 s between trigger activation and relay switching.
- Invert: Reverses the output switching logic to suit normally open/normally closed control requirements. It changes which relay state is used during an event.
Digital Inputs¶
- Digital inputs
- Digital input 1
-
Invert input
-
Forward to
- Digital input 2
-
Invert input
-
Forward to
- Invert input: Reverses input logic.
- Forward to: Select trigger 1–27. A high input activates it; with inversion enabled, a low input activates it.
Serial¶
Select the hardware connected to each serial port. Also assign the serial port to an internal data device under Data Devices. Both steps are needed for correct detection and mapping.
- Serial interfacesTo use serial 3-11, the serial extension is required!
- Serial 1
-
Serial
- Serial 2
-
Serial
Original BSC software-to-hardware mapping: Serial 0 → U1, Serial 1 → U2, Serial 2 → U3. Serial 3–10 require the Serial Extension.
See Supported BMS Units for supported hardware and addressing details. Support is expanded continuously.
Cell Count¶
-
Number of cells
-
Number of individual cells in the battery. Needed, for example, for correct dashboard display.
Filter¶
-
Number of RX errorsNumber of invalid packets after which a fault is reported.
-
Cell voltage deviation%0 = filter disabled
-
The filter detects and suppresses sudden cell voltage jumps, preventing transient erroneous data packets from being used. Its threshold is a percentage relative to the previous valid value. Values beyond that deviation are discarded; the configured reception-error count determines when the state is treated as an error.
- RX error count: Number of consecutive faulty packets tolerated before the state is considered an error. Once exceeded, the timestamp of the last valid packet is no longer updated.
- Cell voltage deviation: Maximum permitted percentage deviation. 0 disables filtering.
OneWire (Sensor Addresses)¶
Enable OneWire and set addresses for up to 64 DS18B20 temperature sensors.
-
Onewire enable
- OW addresses
- OW Adr. 1
-
OW Adr.
- OW Adr. 2
-
OW Adr.
-
Opening the firmware's OneWire configuration page starts periodic bus scans. Detected devices appear at the bottom. Bold addresses identify newly found sensors not yet saved. In the firmware, Copy copies an address to the clipboard.
| Example sensor address | Status |
|---|---|
28:93:e3:95:f0:1:3c:56 |
Previously configured |
28:93:e3:95:f0:1:3c:57 |
New sensor |
28:93:e3:95:f0:1:3c:58 |
Previously configured |
OneWire II (Temperature Offset)¶
Set a correction offset for each of the 64 OneWire temperature sensors.
- OneWire sensors
- Sensor 1
-
Offset°C
- Sensor 2
-
Offset°C
Bluetooth¶
Not Supported in Current Firmware
Bluetooth is not supported by the current firmware.
- BluetoothThe MAC address must use lowercase letters!
- BT Device 1
-
Bluetooth
-
MAC address
-
Deactivate
- BT Device 2
-
Bluetooth
-
MAC address
-
Deactivate
Earlier firmware allowed up to five Bluetooth devices, configured by type and lowercase MAC address. Opening that page scanned periodically and displayed the last five detected devices. See the historical Bluetooth device list.