Trigger
How Triggers Work¶
Internal triggers monitor values such as temperature or voltage and enable responses to potentially dangerous conditions.
Trigger Function
A source activates a trigger when its configured limit is reached. A trigger does not itself perform an action. Configure consumers separately, for example to switch a fan relay or tell the inverter to reduce charging current to 0 A. Up to 27 internal triggers can combine sources and actions flexibly. External systems can also activate them through virtual triggers.
Multiple Sources
- Activation (high): Active when at least one connected source exceeds its limit.
- Deactivation (low): Inactive only when all connected sources return to normal.
Reset Virtual Triggers
Automations using vTriggers must explicitly deactivate them too.
Example
Sensors 2 and 3 monitor a 30 °C threshold. If either exceeds it, trigger 1 activates. Relay 1 can then start a fan while the inverter reduces charging current to limit heat generation.
This separation of flexible sources and configurable actions permits early detection and tailored responses.
Trigger Names¶
- Trigger description
- Trigger 1
-
Trigger
- Trigger 2
-
Trigger
Assign names of up to 16 characters to the 27 triggers. Names appear throughout the system, including trigger selectors.
Trigger Scheduler¶
- Trigger Scheduler
- Scheduler 1
-
Trigger
-
Month
-
Day of week
-
from
-
to
- Scheduler 2
-
Trigger
-
Month
-
Day of week
-
from
-
to
Five independently configurable schedulers activate triggers by time.
Firmware Availability
The scheduler is not available in every firmware version.
- Trigger: Select trigger 1–27.
- Month: Select active months.
- Weekday: Select active weekdays.
- From: Start time.
- Until: End time.