Skip to content

Trigger

How Triggers Work

Internal triggers monitor values such as temperature or voltage and enable responses to potentially dangerous conditions.

Trigger Function

A source activates a trigger when its configured limit is reached. A trigger does not itself perform an action. Configure consumers separately, for example to switch a fan relay or tell the inverter to reduce charging current to 0 A. Up to 27 internal triggers can combine sources and actions flexibly. External systems can also activate them through virtual triggers.

Multiple Sources

  • Activation (high): Active when at least one connected source exceeds its limit.
  • Deactivation (low): Inactive only when all connected sources return to normal.

Reset Virtual Triggers

Automations using vTriggers must explicitly deactivate them too.

Example

Sensors 2 and 3 monitor a 30 °C threshold. If either exceeds it, trigger 1 activates. Relay 1 can then start a fan while the inverter reduces charging current to limit heat generation.

This separation of flexible sources and configurable actions permits early detection and tailored responses.

Trigger Names

    • Trigger description
    • Trigger 1
    • Trigger
       
    • Trigger 2
    • Trigger
       

Assign names of up to 16 characters to the 27 triggers. Names appear throughout the system, including trigger selectors.

Trigger Scheduler

    • Trigger Scheduler
    • Scheduler 1
    • Trigger
       
    • Month
       
    • Day of week
       
    • from
       
    • to
       
    • Scheduler 2
    • Trigger
       
    • Month
       
    • Day of week
       
    • from
       
    • to
       

Five independently configurable schedulers activate triggers by time.

Firmware Availability

The scheduler is not available in every firmware version.

  • Trigger: Select trigger 1–27.
  • Month: Select active months.
  • Weekday: Select active weekdays.
  • From: Start time.
  • Until: End time.